Enums ¶ CANOPEN_KERNEL_ERROR (Enum) DEVICE_STATE (Enum) SDO_MODE (Enum) TRANSITION_STATE (Enum)
CAA CiA 405 ¶ Enums CANOPEN_KERNEL_ERROR (Enum) DEVICE_STATE (Enum) SDO_MODE (Enum) TRANSITION_STATE (Enum) Function Blocks Network management NMT (FunctionBlock) RECV_EMCY (FunctionBlock) RECV_EMCY_DEV (FunctionBlock) Own node id GET_LOCAL_NODE_ID (FunctionBlock) Query state GET_CANOPEN_KERNEL_STATE (FunctionBlock) GET_STATE (FunctionBlock) SDO access SDO_READ4 (FunctionBlock) SDO_READ_DATA (FunctionBlock) SDO_WRITE4 (FunctionBlock) SDO_WRITE_DATA (FunctionBlock) obsolete (only for compatibility) SDO_READ (FunctionBlock) SDO_WRITE (FunctionBlock) Types DEVICE (Alias) SDO_ERROR (Alias)
CANOPEN_KERNEL_ERROR (ENUM) ¶ TYPE CANOPEN_KERNEL_ERROR : Error codes for output ERROR of CiA405 function blocks and return value for GET_CANOPEN_KERNEL_STATE . Attributes: qualified_only InOut: Name Initial Comment CANOPEN_KERNEL_NO_ERROR ANYNUM_TO_WORD(CS.CANOPEN_KERNEL_ERROR.CANOPEN_KERNEL_NO_ERROR) There is no error. CANOPEN_KERNEL_OTHER_ERROR ANYNUM_TO_WORD(CS.CANOPEN_KERNEL_ERROR.CANOPEN_KERNEL_OTHER_ERROR) More information is provided by output ERRORINFO . CANOPEN_KERNEL_DATA_OVERFLOW ANYNUM_TO_WORD(CS.CANOPEN_KERNEL_ERROR.CANOPEN_KERNEL_DATA_OVERFLOW) Lost counter or Tx/Rx error counter is above 0. CANOPEN_KERNEL_TIMEOUT ANYNUM_TO_WORD(CS.CANOPEN_KERNEL_ERROR.CANOPEN_KERNEL_TIMEOUT) A timeout occurred. CANOPEN_KERNEL_CANBUS_OFF ANYNUM_TO_WORD(CS.CANOPEN_KERNEL_ERROR.CANOPEN_KERNEL_CANBUS_OFF) CAN Bus is in BUSOFF or busalarm state. CANOPEN_KERNEL_CAN_ERROR_PASSIVE ANYNUM_TO_WORD(CS.CANOPEN_KERNEL_ERROR.CANOPEN_KERNEL_CAN_ERROR_PASSIVE) CAN Bus is in Error Passive state. CANOPEN_INTERNAL_FB_ERROR ANYNUM_TO_WORD(CS.CANOPEN_KERNEL_ERROR.CANOPEN_INTERNAL_FB_ERROR) internal error CANOPEN_NO_MORE_MEMORY ANYNUM_TO_WORD(CS.CANOPEN_KERNEL_ERROR.CANOPEN_NO_MORE_MEMORY) There is not enough memory. CANOPEN_WRONG_PARAMETER ANYNUM_TO_WORD(CS.CANOPEN_KERNEL_ERROR.CANOPEN_WRONG_PARAMETER) Wrong parameter passed to the function. CANOPEN_NODEID_UNKNOWN ANYNUM_TO_WORD(CS.CANOPEN_KERNEL_ERROR.CANOPEN_NODEID_UNKNOWN) Unknown NodeID. CANOPEN_NETID_UNKNOWN ANYNUM_TO_WORD(CS.CANOPEN_KERNEL_ERROR.CANOPEN_NETID_UNKNOWN) Unknown CAN Network ID (not part of I/O config). CANOPEN_REQUEST_ERROR ANYNUM_TO_WORD(CS.CANOPEN_KERNEL_ERROR.CANOPEN_REQUEST_ERROR) A request error happened. CANOPEN_SDOCHANNEL_UNKNOWN ANYNUM_TO_WORD(CS.CANOPEN_KERNEL_ERROR.CANOPEN_SDOCHANNEL_UNKNOWN) Unknown SDO channel. CANOPEN_NO_DRIVER ANYNUM_TO_WORD(CS.CANOPEN_KERNEL_ERROR.CANOPEN_NO_DRIVER) CAN Driver not found. CANOPEN_CONFIGURATION_ERROR ANYNUM_TO_WORD(CS.CANOPEN_KERNEL_ERROR.CANOPEN_CONFIGURATION_ERROR) At least one SDO abort in configuration phase of a slave. CANOPEN_GUARDING_ERROR ANYNUM_TO_WORD(CS.CANOPEN_KERNEL_ERROR.CANOPEN_GUARDING_ERROR) A guarding error (Heartbeat or Nodeguarding) occured.
DEVICE_STATE (ENUM) ¶ TYPE DEVICE_STATE : Describes the state of the CANopen network layer, as defined in /DS-301/. The states INIT , RESET_COMM , RESET_APP , PRE_OPERATIONAL , STOPPED , OPERATIONAL correspond to the same states in /DS-301/. The state UNKNOWN is used, if the actual state of the device is not known (for example, if no guarding is performed). The state NOT_AVAIL is used, if it is known, that the device is not available (for example, if guarding is performed and the device does not answer). Attributes: qualified_only InOut: Name INIT RESET_COMM RESET_APP PRE_OPERATIONAL STOPPED OPERATIONAL UNKNOWN NOT_AVAIL
SDO_MODE (ENUM) ¶ TYPE SDO_MODE : Defines the different SDO transmission modes. Attributes: qualified_only InOut: Name Initial Comment AUTO ANYNUM_TO_INT(CS.SDO_MODE.AUTO) The client selects the mode automatically EXPEDITED ANYNUM_TO_INT(CS.SDO_MODE.EXPEDITED) The client uses the expedited protocol SEGMENTED ANYNUM_TO_INT(CS.SDO_MODE.SEGMENTED) The client uses segmented transfer protocol BLOCK ANYNUM_TO_INT(CS.SDO_MODE.BLOCK) The client uses block transfer protocol
TRANSITION_STATE (ENUM) ¶ TYPE TRANSITION_STATE : Describes the NMT state transitions for function block GET_STATE . Attributes: qualified_only InOut: Name Initial Comment START_REMOTE_NODE 16#5 Enter DEVICE_STATE.OPERATIONAL STOP_REMOTE_NODE 16#4 Enter DEVICE_STATE.STOPPED ENTER_PRE_OPERATIONAL 16#7F Enter DEVICE_STATE.PRE_OPERATIONAL RESET_NODE 16#6 Reset node RESET_COMMUNICATION 16#7 Reset communication ALL_EXCEPT_NMT_AND_SENDER 16#800 A flag for using in combination with another TRANSITION_STATE (logical OR). Must be used if NMT command should be addressed to all devices ( `` DEVICE``=0) but not to the NMT sender and NMT master (= CANopenManager).
Function Blocks ¶ Network management NMT (FunctionBlock) RECV_EMCY (FunctionBlock) RECV_EMCY_DEV (FunctionBlock) Own node id GET_LOCAL_NODE_ID (FunctionBlock) Query state GET_CANOPEN_KERNEL_STATE (FunctionBlock) GET_STATE (FunctionBlock) SDO access SDO_READ4 (FunctionBlock) SDO_READ_DATA (FunctionBlock) SDO_WRITE4 (FunctionBlock) SDO_WRITE_DATA (FunctionBlock) obsolete (only for compatibility) SDO_READ (FunctionBlock) SDO_WRITE (FunctionBlock)
Network management ¶ NMT (FunctionBlock) RECV_EMCY (FunctionBlock) RECV_EMCY_DEV (FunctionBlock)
NMT (FB) ¶ FUNCTION_BLOCK NMT EXTENDS CiA405Base This function block provides NMT services. The NMT request will be sent to the NodeID specified in input DEVICE . If NMT request should be addressed to all devices (including NMT master and sending device) set DEVICE to 0 . If all devices but not NMT master and sending device should be addressed use the additional flag TRANSITION_STATE.ALL_EXCEPT_NMT_AND_SENDER . InOut: Scope Name Type Initial Comment Inherited from Input NETWORK USINT 1 CAN network number the function block should operate on. Note: It is not the same like the network number in CANBus configurator. The CiA405 NETWORK is calculated by NetID + 1. Example: 1 = CAN0, 2 = CAN1, 3 = CAN2, … CiA405Base ENABLE BOOL FALSE Enables the function block on rising edge. Aborts operation on falling edge. CiA405Base TIMEOUT UDINT 0 Timeout in ms; 0 means no timeout CiA405Base Output CONFIRM BOOL FALSE TRUE : function block finished without error CiA405Base ERROR CANOPEN_KERNEL_ERROR CANOPEN_KERNEL_ERROR.CANOPEN_KERNEL_NO_ERROR Error code: see CANOPEN_KERNEL_ERROR for further details CiA405Base Input DEVICE DEVICE 0 NodeID of destination device (local or remote). 0 means all devices. STATE TRANSITION_STATE 0 The NMT transition which should be performed.
RECV_EMCY (FB) ¶ FUNCTION_BLOCK RECV_EMCY EXTENDS CiA405Base Function block checks if an emergency object has been received from any DEVICE . If the function block has finished its action without any error, output CONFIRM is changed to TRUE and ERROR to 0. If DEVICE is 0 all devices are error free. If an EMCY is pending or an EMCY error reset was received output DEVICE contains the NodeID of the corresponding device and ERRORINFO contains the EMCY information. Note An EMCY will be returned as long as it is pending. An EMCY error reset (Variable EMCY_ERROR_CODE of EMCY_ERROR is zero) is returned only once. If an error occurred while checking for an emergency, CONFIRM is set to FALSE and ERROR is set to the corresponding error value. InOut: Scope Name Type Initial Comment Inherited from Input NETWORK USINT 1 CAN network number the function block should operate on. Note: It is not the same like the network number in CANBus configurator. The CiA405 NETWORK is calculated by NetID + 1. Example: 1 = CAN0, 2 = CAN1, 3 = CAN2, … CiA405Base ENABLE BOOL FALSE Enables the function block on rising edge. Aborts operation on falling edge. CiA405Base TIMEOUT UDINT 0 Timeout in ms; 0 means no timeout CiA405Base Output CONFIRM BOOL FALSE TRUE : function block finished without error CiA405Base ERROR CANOPEN_KERNEL_ERROR CANOPEN_KERNEL_ERROR.CANOPEN_KERNEL_NO_ERROR Error code: see CANOPEN_KERNEL_ERROR for further details CiA405Base DEVICE DEVICE 0 EMCY received: DEVICE contains the NODEID of the sending device; no EMCY received: value is 0 ERRORINFO EMCY_ERROR EMCY information