DeviceStatusT (STRUCT) ¶ TYPE DeviceStatusT : STRUCT
IoDrvModbusTCPSlave.Enable (PROP) ¶ PROPERTY Enable : BOOL
IoDrvModbusTCPSlave.UpdateCommunicationSettings (METH) ¶ METHOD UpdateCommunicationSettings : DINT Change the TCP-Port number. Existing TCP Connection will be aborted InOut: Scope Name Type Initial Comment Return UpdateCommunicationSettings DINT Input uiPortNr UINT 502 TCP-Port Number used by Modbus Server
Library Information ¶ GetLibVersion (Function) GetLibVersionNumber (Function) IsLibReleased (Function)
GetLibVersion (FUN) ¶ FUNCTION GetLibVersion : VERSION This function has been automatically generated from the project information. InOut: Scope Name Type Return GetLibVersion VERSION
GetLibVersionNumber (FUN) ¶ FUNCTION GetLibVersionNumber : DWORD This function has been automatically generated from the project information. InOut: Scope Name Type Return GetLibVersionNumber DWORD
ClientRequestReadWriteMultipleRegistersWide (FB) ¶ FUNCTION_BLOCK ClientRequestReadWriteMultipleRegistersWide EXTENDS ModbusFB.ClientRequest ReadWriteMultipleRegister client request (FC23) for registers > 16bit. For details about client request see |ClientRequest| . For details about “wide registers” and endianess see ServerTCP_extended or ServerSerial_extended . Please note: The write operation is performed before the read. Please visit https://forge.codesys.com/prj/codesys-example/modbus/home to find examples. InOut: Scope Name Type Initial Comment Inherited from Input xExecute BOOL Rising edge: Starts defined operation FALSE : Resets the defined operation after ready condition was reached ETrigTo udiTimeOut UDINT Max. operating time for executing [µs], 0: No operating time limit ETrigTo Output xDone BOOL Ready condition reached ETrigTo xBusy BOOL Operation is running ETrigTo xError BOOL Error condition reached ETrigTo Inout rClient Client Reference to |Client| . ClientRequest Input uiUnitId UINT 0 Unit-Id to send the request to. ClientRequest udiReplyTimeout UDINT (50 * 1000) 50 ms ClientRequest uiMaxRetries UINT 0 Maximum number of request retries in case of “reply timeout”. ClientRequest Output eErrorID Error Error status ClientRequest eException ExceptionCodes Request exception code. ClientRequest uiRetryCnt UINT 0 Number of request retries in case of “reply timeout”. ClientRequest Input uiWriteStartItem UINT 0 First “data item” to write. uiWriteQuantity UINT 1 Number of “data items” to write. pWriteData POINTER TO BYTE 0 Pointer to write data. uiWriteDataItemSize UINT write “data item” size / register width (in bytes). The ClientRequest has to know about the “data item” size a-priori to provide memory for result data. In case the server unexpectedly does have a different “data item” size than assumed, the ClientRequest can not succeed. uiReadStartItem UINT 0 First “data item” to read. uiReadQuantity UINT 1 Number of “data items” to read. pReadData POINTER TO BYTE 0 Pointer to read data. uiReadDataItemSize UINT read “data item” size / register width (in bytes).
ClientRequestWriteMultipleRegistersWide (FB) ¶ FUNCTION_BLOCK ClientRequestWriteMultipleRegistersWide EXTENDS ModbusFB.ClientRequestWriteMultiple WriteMultipleRegisters client request (FC16) for registers > 16bit. For details about client request see |ClientRequest| . For details about “wide registers” and endianess see ServerTCP_extended or ServerSerial_extended . Please visit https://forge.codesys.com/prj/codesys-example/modbus/home to find examples. InOut: Scope Name Type Initial Comment Inherited from Input xExecute BOOL Rising edge: Starts defined operation FALSE : Resets the defined operation after ready condition was reached ETrigTo udiTimeOut UDINT Max. operating time for executing [µs], 0: No operating time limit ETrigTo Output xDone BOOL Ready condition reached ETrigTo xBusy BOOL Operation is running ETrigTo xError BOOL Error condition reached ETrigTo Inout rClient Client Reference to |Client| . ClientRequest Input uiUnitId UINT 0 Unit-Id to send the request to. ClientRequest udiReplyTimeout UDINT (50 * 1000) 50 ms ClientRequest uiMaxRetries UINT 0 Maximum number of request retries in case of “reply timeout”. ClientRequest Output eErrorID Error Error status ClientRequest eException ExceptionCodes Request exception code. ClientRequest uiRetryCnt UINT 0 Number of request retries in case of “reply timeout”. ClientRequest Input uiStartItem UINT 0 First “data item” to write. ClientRequestWriteMultiple uiQuantity UINT 1 Number of “data items” to write. ClientRequestWriteMultiple pData POINTER TO UINT 0 Pointer to data. uiDataItemSize UINT “data item” size / register width (in bytes).
ServerSerial_extended (FB) ¶ FUNCTION_BLOCK ServerSerial_extended EXTENDS ModbusFB.ServerSerial MODBUS Serial server (slave) with non-standard extensions. ServerSerial_extended actually supports beyond the ServerSerial features: - “wide register” (registers > 16bit) Other non-standard extensions might be added here, but not on ServerSerial. “wide registers” and endianess ¶ The MODBUS standard defines the length of input / holding registers to read/write with 16-bit - no way out of this. The message definitions in the MODBUS standard come with some room for non-standard interpretation. FC03 Read Holding Registers should be used as an example here: Request: Quantity of Registers Response: Byte count So a non-standard MODBUS server can inform a client in the response indirectly about the register width (Response:Byte count = Request:Quantity of Registers * register width in Bytes). This fact leaded some vendors to implement MODBUS devices with registers > 16bit. Because the CODESYS ModbusFB lib should be usable with such non-standard devices (clients as well as servers) there is a Server*_extended and some related ClientRequest*RegistersWide in this library. Following client requests can be used with “wide registers”: - Read Holding Registers - Read Input Registers - Write Multiple registers - Read/Write Multiple registers Following client requests can not be used with “wide registers” because of their MODBUS protocol data unit (PDU) definition: - Write Single Register - Mask Write Register because the “data item” width is explicitly defined to be 16bit. A standard MODBUS client requesting register data from such a non-standard MODBUS server, unfortunately requesting register data from a register > 16bit gets confronted with an invalid Response: Byte count <> Quantity of Registers * 2, and will most likely drop such a response as invalid or less likely put out error/warning/information on this fact. The MODBUS standard defines byte ordering in MODBUS messages to read/write 16-bit registers. The MODBUS standard doesnt define anything beyond this - so there is no rule for byte ordering in “wide registers”. This ServerSerial_extended is using the same byte ordering for register data > 16bit as defined in the MODBUS standard (“big-Endian” representation). So for example register size 32bit value 0x12345678 - the first byte sent is 0x12 then 0x34, 0x56, 0x78. Please visit https://forge.codesys.com/prj/codesys-example/modbus/home to find examples. InOut: Scope Name Type Initial Comment Inherited from Input xEnable BOOL FALSE Enables the server, take over the configuration information fcsSupported and dataModel. If the “data model” (tableDefinitions) contains configuration errors, the Server will not got busy (xBusy = FALSE). Server fcsSupported SupportedFcs Constants.SUPPORTED_FCS_SIMPLE_SERVER Supported “function codes”, accepted at xEnable FALSE => TRUE. In case fcsSupported is not assigned by the application it defaults to |Constants.SUPPORTED_FCS_SIMPLE_SERVER| . Server dataModel TableDefinitions “data model”, accepted at xEnable FALSE => TRUE. Server tInactivityInfoTime UDINT 0 “inactivity info time” (in milliseconds). If no valid requests are received in this time xInactive is signaling inactivity - default = 0 -> no “inactivity info”. Server Output xRunning BOOL Server is up and running, waiting for requests. Server xError BOOL Error Server eErrorID Error Error status Server xInactive BOOL No valid requests received for tInactivityTimeOut. Server udiNumMsgRecv UDINT Number of request messages received since enabling the Server. Server udiNumMsgReply UDINT Number of reply messages send since enabling the Server. Server udiNumMsgExcReply UDINT Number of exception reply messages send since enabling the Server. Server udiNumMsgExcReplyIllFct UDINT Number of exception reply messages send since enabling the Server, signaling illegal function. Server udiNumMsgExcReplyIllDataAdr UDINT Number of exception reply messages send since enabling the Server, signaling illegal data address. Server udiNumMsgExcReplyIllDataValue UDINT Number of exception reply messages send since enabling the Server, signaling illegal data value. Server xReadRequest BOOL Read request(s) happened since last call, rejected requests included. Server udiNumReadRequests UDINT Read request counter, rejected requests included. Server xWriteRequest BOOL Write request(s) happened since last call, rejected requests included. Server udiNumWriteRequests UDINT Write request counter, rejected requests included. Server Input uiUnitId UINT 1 Unit-Id / Slave address. Only read when rising edge on xEnable occurs. Slave address has to be in range 1 .. 247 according to MODBUS standard. ServerSerial iPort SysCom.SYS_COM_PORTS SysCom.SYS_COM_PORTS.SYS_COMPORT_NONE Serial port. Only read when rising edge on xEnable occurs. ServerSerial dwBaudrate SysCom.SYS_COM_BAUDRATE SysCom.SYS_COM_BAUDRATE.SYS_BR_115200 Baud rate. Only read when rising edge on xEnable occurs. ServerSerial byDataBits BYTE 8 Number of data bits/BYTE, 4-8. Only read when rising edge on xEnable occurs. ServerSerial eParity SysCom.SYS_COM_PARITY SysCom.SYS_COM_PARITY.SYS_NOPARITY Parity. Only read when rising edge on xEnable occurs. ServerSerial eStopBits SysCom.SYS_COM_STOPBITS SysCom.SYS_COM_STOPBITS.SYS_ONESTOPBIT Stop bits. Only read when rising edge on xEnable occurs. ServerSerial eDTRcontrol SysCom.SYS_COM_DTR_CONTROL SysCom.SYS_COM_DTR_CONTROL.SYS_DTR_CONTROL_DISABLE DTR control. Only read when rising edge on xEnable occurs. ServerSerial eRTScontrol SysCom.SYS_COM_RTS_CONTROL SysCom.SYS_COM_RTS_CONTROL.SYS_RTS_CONTROL_DISABLE RTS control. Only read when rising edge on xEnable occurs. ServerSerial eRtuAscii RtuAscii RtuAscii.RTU RTU / ASCII. Only read when rising edge on xEnable occurs. ServerSerial udiLogOptions UDINT LoggingOptions.ServerStartStop Logging options. ServerSerial
Server ¶ ServerSerial_extended (FunctionBlock) “wide registers” and endianess ServerTCP_extended (FunctionBlock) “wide registers” and endianess